On any AWG wire gauge chart, a smaller number means a thicker wire: in the American Wire Gauge system, 14 AWG copper is 0.0641 in (1.63 mm) across and is rated 15 A for most branch circuits, while 12 AWG is 0.0808 in (2.05 mm) and rated 20 A. Every 3 gauge steps roughly doubles the cross-sectional area, and every 6 steps doubles the diameter.
The chart below lists diameter, area, resistance and the NEC copper ampacity for the common sizes from 18 AWG to 4/0. Below it you will find how to read the temperature columns, how to choose a wire size for a circuit, and why long runs need a bigger wire than the ampacity table suggests. For an instant answer for your circuit, use the wire gauge calculator.
AWG wire gauge chart
Ampacities are for insulated copper conductors, not more than three current-carrying conductors in a raceway or cable, at 30°C (86°F) ambient, from NEC Table 310.16 (2020/2023 editions). Resistance is DC resistance of stranded uncoated copper at 75°C from NEC Chapter 9, Table 8.
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Area (kcmil) | Ω per 1,000 ft | 60°C | 75°C | 90°C |
|---|---|---|---|---|---|---|---|---|
| 18 | 0.0403 | 1.024 | 0.823 | 1.62 | 7.95 | — | — | 14 A |
| 16 | 0.0508 | 1.291 | 1.31 | 2.58 | 4.99 | — | — | 18 A |
| 14 | 0.0641 | 1.628 | 2.08 | 4.11 | 3.14 | 15 A | 20 A | 25 A |
| 12 | 0.0808 | 2.053 | 3.31 | 6.53 | 1.98 | 20 A | 25 A | 30 A |
| 10 | 0.1019 | 2.588 | 5.26 | 10.38 | 1.24 | 30 A | 35 A | 40 A |
| 8 | 0.1285 | 3.264 | 8.37 | 16.51 | 0.778 | 40 A | 50 A | 55 A |
| 6 | 0.1620 | 4.115 | 13.30 | 26.25 | 0.491 | 55 A | 65 A | 75 A |
| 4 | 0.2043 | 5.189 | 21.15 | 41.74 | 0.308 | 70 A | 85 A | 95 A |
| 3 | 0.2294 | 5.827 | 26.67 | 52.62 | 0.245 | 85 A | 100 A | 115 A |
| 2 | 0.2576 | 6.544 | 33.63 | 66.36 | 0.194 | 95 A | 115 A | 130 A |
| 1 | 0.2893 | 7.348 | 42.41 | 83.69 | 0.154 | 110 A | 130 A | 145 A |
| 1/0 | 0.3249 | 8.251 | 53.48 | 105.6 | 0.122 | 125 A | 150 A | 170 A |
| 2/0 | 0.3648 | 9.266 | 67.43 | 133.1 | 0.0967 | 145 A | 175 A | 195 A |
| 3/0 | 0.4096 | 10.405 | 85.03 | 167.8 | 0.0766 | 165 A | 200 A | 225 A |
| 4/0 | 0.4600 | 11.684 | 107.2 | 211.6 | 0.0608 | 195 A | 230 A | 260 A |
Diameters are for a single solid conductor; stranded wire of the same gauge has the same copper area but a slightly larger overall diameter. Look up any gauge, including sizes finer than 18 AWG, with the wire diameter calculator.
How the AWG numbers work
AWG is a logarithmic scale defined so that 36 AWG is exactly 0.005 in and 0000 (4/0) is exactly 0.46 in, with 39 equal ratio steps between them. The diameter of any gauge n is:
d (mm) = 0.127 × 92^((36 − n) ÷ 39) d (in) = 0.005 × 92^((36 − n) ÷ 39) area (mm²) = π ÷ 4 × d²
For 1/0, 2/0, 3/0 and 4/0 use n = 0, −1, −2 and −3. Each step changes the diameter by a factor of about 1.123 and the area by about 1.261, which gives the handy rules of thumb: 3 gauges = double (or half) the area and resistance, and 10 gauges = ten times the area. For example, 10 AWG has 5.26 mm²; three steps thinner, 13 AWG has 2.62 mm² — half the area and about double the resistance — and 20 AWG, ten steps thinner, has 0.52 mm², about one-tenth.
Sizes above 4/0 are given in kcmil (thousands of circular mils). A circular mil is the area of a circle 0.001 in across, so a wire’s area in circular mils equals its diameter in mils squared: 12 AWG is 80.8 mils, and 80.8² ≈ 6,530 cmil. Metric cable is sold by mm² instead — 2.5 mm² sits between 14 AWG (2.08) and 12 AWG (3.31). The cable size calculator works in mm².
Reading the 60°C, 75°C and 90°C columns
The three ampacity columns correspond to the temperature rating of the insulation. Hotter-rated insulation tolerates more current, but you can only use a column if every part of the circuit — wire, breaker and device terminals — is rated for that temperature.
- 60°C: NM-B (Romex) cable must be sized from this column (NEC 334.80), and terminations on equipment rated 100 A or less, or marked for 14–1 AWG, default to 60°C unless listed otherwise (NEC 110.14(C)).
- 75°C: the usual column for THWN wire in conduit and for most breakers and panel lugs, which are marked 60/75°C.
- 90°C: THHN, XHHW-2 and similar. The 90°C value is mainly a starting point for derating when you have many conductors in a raceway or high ambient temperatures; the final ampacity still may not exceed the terminal rating.
There is one more cap: NEC 240.4(D), the “small conductor rule,” limits overcurrent protection to 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper, no matter which column you read. That is why 12 AWG THHN shows 25 A at 75°C but still goes on a 20 A breaker.
Choosing a wire size
For typical residential copper wiring, these pairings follow from the chart and the small conductor rule:
| Breaker | Copper wire (minimum) | Typical loads |
|---|---|---|
| 15 A | 14 AWG | Lighting, general bedroom and living room outlets |
| 20 A | 12 AWG | Kitchen countertop, bathroom, laundry and garage outlets |
| 30 A | 10 AWG | Electric dryer, 50-gallon water heater, small A/C units |
| 40 A | 8 AWG | Electric range or cooktop (NM-B at 60°C = 40 A) |
| 50 A | 6 AWG NM-B, or 8 AWG THHN in conduit at 75°C | Range, EV charger (40 A continuous), subpanel |
| 60 A | 6 AWG THHN/THWN in conduit (75°C) | Subpanel, large EV charger, tankless heater |
Work through the decision in this order:
- Find the load current. Use I = P ÷ V, or the kVA to amps calculator for transformers and three-phase loads. A 4,500 W water heater at 240 V draws 18.75 A.
- Allow for continuous loads. A load that runs three hours or more must not exceed 80% of the breaker rating, so size the circuit at 125% of the load: 18.75 × 1.25 = 23.4 A, which means a 25 A or 30 A breaker and at least 10 AWG.
- Pick the wire from the correct temperature column, then apply any derating for bundling or hot locations.
- Check voltage drop on long runs and upsize if needed (next section).
Long runs: voltage drop decides
Ampacity keeps wire from overheating; it says nothing about how much voltage you lose along the way. The NEC informational notes recommend no more than 3% drop on a branch circuit and 5% total from service to load. A quick single-phase estimate:
VD = 2 × K × I × L ÷ CM K = 12.9 for copper (21.2 for aluminum), L = one-way length in feet, CM = wire area in circular mils
Example: a 20 A load at 120 V, 100 ft from the panel.
- 12 AWG (6,530 cmil): 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.90 V = 6.6% — too much.
- 10 AWG (10,380 cmil): 4.97 V = 4.1% — better, still above 3%.
- 8 AWG (16,510 cmil): 3.13 V = 2.6% — meets the 3% recommendation.
So a circuit that only needs 12 AWG for ampacity may need 8 AWG to perform well at the end of a long run. The same load on 240 V has half the percentage drop, which is one reason well pumps and shop subpanels are usually fed at 240 V. Run your own numbers in the voltage drop calculator, and see Ohm’s law explained for the physics behind it.
Aluminum and copper-clad wire
Aluminum has about 61% of copper’s conductivity, so it needs a size roughly two gauges larger for the same ampacity. It is common and code-compliant for service entrance and feeder conductors (for example, a 200 A dwelling service is commonly fed with 4/0 aluminum where 2/0 copper would otherwise be used), but requires terminals rated AL/CU and proper torque. Small-gauge aluminum branch wiring from the 1960s–70s is a known fire risk and should be evaluated by an electrician.
Safety note: this chart is a reference summary, not a substitute for the NEC or your local amendments. Ampacity depends on insulation type, installation method, ambient temperature and the number of conductors. Electrical work should follow your local code, be permitted and inspected where required, and is best performed by a licensed electrician.
Frequently Asked Questions
What size wire do I need for a 20 amp circuit?
Use at least 12 AWG copper. The NEC small conductor rule limits 12 AWG to a 20 A breaker, and long runs may need 10 AWG to keep voltage drop under 3%.
Is a lower AWG number thicker?
Yes. In AWG, smaller numbers are thicker wires. 10 AWG is thicker than 12 AWG, and 4/0 is the largest size before kcmil sizes begin.
How many amps can 14 gauge wire carry?
14 AWG copper is rated 15 A at 60°C, 20 A at 75°C and 25 A at 90°C in NEC Table 310.16, but it may not be protected by a breaker larger than 15 A in most applications.
What is the difference between 60°C, 75°C and 90°C ampacity?
They match the insulation temperature rating. You must use the lowest rating of any part of the circuit, which is usually the 60°C or 75°C rating of the breaker and device terminals.
What AWG is 2.5 mm² wire?
2.5 mm² falls between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). It is roughly 13 AWG, a size rarely sold in the US.