This voltage drop calculator shows how many volts are lost along a cable run and whether the wire is big enough. Enter the system type, source voltage, load current, one-way distance, conductor material and wire size — in AWG/kcmil or metric mm². You get the drop in volts and percent, the voltage left at the load, and the smallest wire size that keeps the drop under 3%.
How to use the voltage drop calculator
- Choose single-phase/DC (two conductors carry the current) or three-phase.
- Enter the source voltage — 120 V, 240 V, 208 V, 480 V, 12 V DC and so on.
- Enter the load current in amps. For continuous loads use the actual running current.
- Enter the one-way length from the panel to the load, in feet or meters. The calculator accounts for the return path.
- Pick copper or aluminum and the wire size, then read the verdict.
Voltage drop formula
Single-phase / DC: VD = 2 × K × I × L ÷ CM Three-phase: VD = 1.732 × K × I × L ÷ CM Percent drop = VD ÷ Source voltage × 100 K = resistivity: 12.9 Ω·cmil/ft (copper), 21.2 Ω·cmil/ft (aluminum) at 75 °C I = current (A) L = one-way length (ft) CM = conductor area in circular mils (1 mm² = 1,973.5 cmil)
This is the standard method used by electricians and in NEC handbook examples. It ignores reactance, which is reasonable for conductors up to about 1/0 AWG on typical power-factor loads.
Example: 20 A circuit, 100 ft run at 120 V
- 12 AWG copper (6,530 cmil): VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.90 V
- Percent = 7.90 ÷ 120 = 6.6% — too much; the load sees only 112 V
- Minimum area for 3%: 2 × 12.9 × 20 × 100 ÷ (0.03 × 120) = 14,333 cmil → 8 AWG
- With 8 AWG: VD = 3.13 V = 2.6% ✅
Maximum distance for a 3% voltage drop (copper)
One-way length at full rated current on a single-phase circuit:
| Wire size | Current | At 120 V | At 240 V |
|---|---|---|---|
| 14 AWG | 15 A | 38 ft | 76 ft |
| 12 AWG | 20 A | 46 ft | 91 ft |
| 10 AWG | 30 A | 48 ft | 97 ft |
| 8 AWG | 40 A | 58 ft | 115 ft |
| 6 AWG | 55 A | 67 ft | 133 ft |
At half the current the allowable distance doubles. Low-voltage DC systems (12 V or 24 V solar, RV and landscape lighting) are far more sensitive: at 12 V the same distances shrink to one tenth of the 120 V column.
How much voltage drop is acceptable?
- NEC informational notes (210.19 and 215.2) recommend no more than 3% on a branch circuit and 5% total for feeder plus branch. They are recommendations, not mandatory rules, but many inspectors and specs enforce them.
- IEC 60364 / BS 7671 allow 3% for lighting and 5% for other uses from the supply point.
- Sensitive equipment such as motors, compressors and EV chargers starts poorly and runs hot when the drop is high.
Ways to reduce voltage drop
- Upsize the conductor — every 3 AWG sizes roughly halves the resistance.
- Use a higher voltage: the same power at 240 V draws half the current of 120 V, which cuts percent drop by four times.
- Shorten the run or move the subpanel closer to the loads.
- Choose copper over aluminum, or upsize aluminum by about two AWG sizes.
Voltage drop is only half of wire sizing — the conductor must also carry the current safely. Check ampacity with the wire gauge calculator, or work backwards from an allowed drop with the cable size calculator.
Related calculators
- Wire Gauge Calculator
- Cable Size Calculator
- Cable Length Calculator
- kVA to Amps Calculator
- Electricity Cost Calculator
Frequently Asked Questions
How do you calculate voltage drop?
For single-phase or DC circuits, multiply 2 × resistivity × current × one-way length and divide by the wire area in circular mils. For copper use 12.9; a 20 A load on 100 ft of 12 AWG (6,530 cmil) loses about 7.9 V.
What is an acceptable voltage drop?
The NEC recommends a maximum of 3% on a branch circuit and 5% in total for feeder plus branch circuit. On a 120 V circuit, 3% is 3.6 V.
What size wire do I need for 100 feet at 20 amps?
At 120 V, 12 AWG copper gives about a 6.6% drop over 100 feet, so 10 AWG (4.1%) or 8 AWG (2.6%) is needed to meet the 3% guideline. At 240 V, 10 AWG keeps the drop near 2.1%.
Does voltage drop use one-way or round-trip length?
Enter the one-way length. The formula multiplies by 2 for single-phase and DC circuits (current flows out and back) and by 1.732 for three-phase circuits.
Is aluminum wire worse for voltage drop?
Yes. Aluminum has about 64% higher resistance than copper, so it needs to be roughly two AWG sizes larger for the same voltage drop.