This voltage drop calculator shows how many volts are lost along a cable run and whether the wire is big enough. Enter the system type, source voltage, load current, one-way distance, conductor material and wire size — in AWG/kcmil or metric mm². You get the drop in volts and percent, the voltage left at the load, and the smallest wire size that keeps the drop under 3%.

How to use the voltage drop calculator

  1. Choose single-phase/DC (two conductors carry the current) or three-phase.
  2. Enter the source voltage — 120 V, 240 V, 208 V, 480 V, 12 V DC and so on.
  3. Enter the load current in amps. For continuous loads use the actual running current.
  4. Enter the one-way length from the panel to the load, in feet or meters. The calculator accounts for the return path.
  5. Pick copper or aluminum and the wire size, then read the verdict.

Voltage drop formula

Single-phase / DC:  VD = 2 × K × I × L ÷ CM
Three-phase:        VD = 1.732 × K × I × L ÷ CM
Percent drop        = VD ÷ Source voltage × 100

K  = resistivity: 12.9 Ω·cmil/ft (copper), 21.2 Ω·cmil/ft (aluminum) at 75 °C
I  = current (A)     L = one-way length (ft)
CM = conductor area in circular mils (1 mm² = 1,973.5 cmil)

This is the standard method used by electricians and in NEC handbook examples. It ignores reactance, which is reasonable for conductors up to about 1/0 AWG on typical power-factor loads.

Example: 20 A circuit, 100 ft run at 120 V

  • 12 AWG copper (6,530 cmil): VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.90 V
  • Percent = 7.90 ÷ 120 = 6.6% — too much; the load sees only 112 V
  • Minimum area for 3%: 2 × 12.9 × 20 × 100 ÷ (0.03 × 120) = 14,333 cmil → 8 AWG
  • With 8 AWG: VD = 3.13 V = 2.6% ✅

Maximum distance for a 3% voltage drop (copper)

One-way length at full rated current on a single-phase circuit:

Wire size Current At 120 V At 240 V
14 AWG 15 A 38 ft 76 ft
12 AWG 20 A 46 ft 91 ft
10 AWG 30 A 48 ft 97 ft
8 AWG 40 A 58 ft 115 ft
6 AWG 55 A 67 ft 133 ft

At half the current the allowable distance doubles. Low-voltage DC systems (12 V or 24 V solar, RV and landscape lighting) are far more sensitive: at 12 V the same distances shrink to one tenth of the 120 V column.

How much voltage drop is acceptable?

  • NEC informational notes (210.19 and 215.2) recommend no more than 3% on a branch circuit and 5% total for feeder plus branch. They are recommendations, not mandatory rules, but many inspectors and specs enforce them.
  • IEC 60364 / BS 7671 allow 3% for lighting and 5% for other uses from the supply point.
  • Sensitive equipment such as motors, compressors and EV chargers starts poorly and runs hot when the drop is high.

Ways to reduce voltage drop

  • Upsize the conductor — every 3 AWG sizes roughly halves the resistance.
  • Use a higher voltage: the same power at 240 V draws half the current of 120 V, which cuts percent drop by four times.
  • Shorten the run or move the subpanel closer to the loads.
  • Choose copper over aluminum, or upsize aluminum by about two AWG sizes.

Voltage drop is only half of wire sizing — the conductor must also carry the current safely. Check ampacity with the wire gauge calculator, or work backwards from an allowed drop with the cable size calculator.

Related calculators

Frequently Asked Questions

How do you calculate voltage drop?

For single-phase or DC circuits, multiply 2 × resistivity × current × one-way length and divide by the wire area in circular mils. For copper use 12.9; a 20 A load on 100 ft of 12 AWG (6,530 cmil) loses about 7.9 V.

What is an acceptable voltage drop?

The NEC recommends a maximum of 3% on a branch circuit and 5% in total for feeder plus branch circuit. On a 120 V circuit, 3% is 3.6 V.

What size wire do I need for 100 feet at 20 amps?

At 120 V, 12 AWG copper gives about a 6.6% drop over 100 feet, so 10 AWG (4.1%) or 8 AWG (2.6%) is needed to meet the 3% guideline. At 240 V, 10 AWG keeps the drop near 2.1%.

Does voltage drop use one-way or round-trip length?

Enter the one-way length. The formula multiplies by 2 for single-phase and DC circuits (current flows out and back) and by 1.732 for three-phase circuits.

Is aluminum wire worse for voltage drop?

Yes. Aluminum has about 64% higher resistance than copper, so it needs to be roughly two AWG sizes larger for the same voltage drop.