This admittance calculator converts a series impedance Z = R + jX into its admittance Y = G + jB, the reciprocal of impedance, in siemens (S). Enter the resistance and the reactance in ohms (positive X for an inductive load, negative X for a capacitive load) and the tool returns the conductance G and the susceptance B as a complex number rounded to three decimals.
How to calculate admittance
Admittance is simply 1 ÷ Z. Because Z is complex, you multiply the top and bottom by the complex conjugate R − jX, which splits the result into a real and an imaginary part:
Y = 1 / Z = 1 / (R + jX) = (R − jX) / (R² + X²) G = R / (R² + X²) conductance, S B = −X / (R² + X²) susceptance, S |Y| = √(G² + B²) = 1 / |Z| θY = −θZ = −atan(X / R)
Where R is resistance (Ω), X is reactance (Ω), G is conductance (S) and B is susceptance (S). One siemens equals 1/Ω (older texts write it as “mho”, ℧). The calculator displays the result as G − (X/|Z|²) j, so an inductive impedance gives a minus sign in front of the j term and a capacitive impedance gives a plus sign.
Note that G is not 1/R unless the reactance is zero. A 30 Ω resistor in series with 40 Ω of inductive reactance has a conductance of 0.012 S, not 0.033 S.
Sign conventions
- Inductive load (X = +ωL): susceptance is negative, B = −1/(ωL) for a pure inductor.
- Capacitive load (X = −1/(ωC)): susceptance is positive, B = +ωC for a pure capacitor.
- Some power-systems texts define Y = G − jB so that inductive susceptance is a positive number. The magnitudes are identical; only the sign of B flips, so always check which convention a textbook or software package uses.
Worked examples
- Pure resistor, 50 Ω: R = 50, X = 0 → Y = 0.02 − 0 j S (20 mS). This is the conductance of a standard RF termination.
- Inductive load, 30 + j40 Ω: R² + X² = 900 + 1600 = 2500. G = 30/2500 = 0.012 S, B = −40/2500 = −0.016 S → 0.012 − 0.016 j S. |Y| = 0.02 S = 1/50 Ω, and |Z| = 50 Ω as expected.
- Capacitive load, 30 − j40 Ω: same magnitude, opposite sign → 0.012 + 0.016 j S.
- Motor-like load, 8 + j6 Ω: R² + X² = 100 → 0.08 − 0.06 j S. The 0.8 power factor (8/10) is the same whether you read it from Z or from Y.
- RL branch at 60 Hz: 20 Ω in series with 100 mH gives X = 2π × 60 × 0.1 = 37.7 Ω. The calculator returns 0.011 − 0.021 j S.
Why engineers use admittance
Admittances in parallel add directly, just as impedances in series add. That makes Y the natural quantity for parallel branches, nodal analysis and power-system bus matrices (the Y-bus). To combine two parallel branches, convert each to Y, add the G parts and the B parts, then invert back to Z if you need an impedance.
Example: a 30 + j40 Ω branch (0.012 − 0.016j S) in parallel with a 30 − j40 Ω branch (0.012 + 0.016j S) gives Y = 0.024 + 0j S, i.e. a purely resistive 41.7 Ω. The reactive parts cancel, which is exactly what power-factor correction does.
Reference table
| Impedance Z (Ω) | |Z| (Ω) | Admittance Y (S) | |Y| (mS) |
|---|---|---|---|
| 25 + j0 | 25 | 0.04 − 0 j | 40 |
| 50 + j0 | 50 | 0.02 − 0 j | 20 |
| 8 + j6 | 10 | 0.08 − 0.06 j | 100 |
| 30 + j40 | 50 | 0.012 − 0.016 j | 20 |
| 40 − j30 | 50 | 0.016 + 0.012 j | 20 |
| 0 + j50 (pure L) | 50 | 0 − 0.02 j | 20 |
| 300 + j400 | 500 | 0.001 − 0.002 j (0.0012 − 0.0016 j exact) | 2 |
Tips and common mistakes
- High impedances: the output is rounded to 0.001 S, so anything above roughly 2 kΩ shows as zero. Enter R and X in kilohms instead; the result is then in millisiemens (mS). For 3 + j4 kΩ you get 0.12 − 0.16 j mS.
- Do not invert R and X separately. 1/R and −1/X are only correct for elements that are already in parallel. For a series R–X pair, always use R/(R² + X²) and −X/(R² + X²).
- Reactance depends on frequency. Compute X = 2πfL or X = −1/(2πfC) at the operating frequency first.
- To get the equivalent parallel circuit, invert G and B individually: Rp = 1/G and Xp = −1/B. For 30 + j40 Ω that is 83.3 Ω in parallel with +j62.5 Ω.
Related calculators
- AC Power Calculator
- Power Factor Calculator
- Parallel Resistance Calculator
- Parallel Inductance Calculator
- Figure of Merit Calculator
Frequently Asked Questions
What is admittance?
Admittance Y is the reciprocal of impedance, Y = 1/Z, and measures how easily alternating current flows through a circuit. It is measured in siemens (S) and has a real part, conductance G, and an imaginary part, susceptance B.
How do I calculate admittance from resistance and reactance?
Divide by R² + X²: G = R/(R² + X²) and B = −X/(R² + X²). For 30 + j40 Ω, Y = 0.012 − 0.016j S.
Is conductance the same as 1/R?
Only when the reactance is zero. With reactance present, G = R/(R² + X²), which is always smaller than 1/R.
Why is the susceptance of an inductor negative?
Because Y = 1/(jωL) = −j/(ωL). Under the common Y = G + jB convention, inductive susceptance is negative and capacitive susceptance (B = ωC) is positive.
What is a siemens?
The SI unit of conductance and admittance, equal to one reciprocal ohm (1/Ω). It was formerly called the mho. A 50 Ω resistor has an admittance of 0.02 S, or 20 mS.