Transformer Conductor Size Calculator

Advertisement
Advertisement
Current
A
Current Density
Amm-2

This transformer conductor size calculator finds the wire cross-section needed for a winding from its current and a chosen current density. Enter the values above to size the conductor.

Formulas

Current   I = VA ÷ (√3 × VL)   (three phase)
Wire area A = I ÷ current density (A/mm²)

Example

10 kVA, 400 V, 3-phase: I = 14.4 A; at 2.3 A/mm², area = 14.4 ÷ 2.3 = 6.3 mm².

Related calculators

Frequently Asked Questions

How do I size transformer winding wire?

Divide the winding current by a safe current density, often 2 to 3 A/mm2, to get the conductor cross-section.

What current density should I use?

2 to 3 A/mm2 is typical for copper windings; lower density runs cooler but uses more copper.

Does this apply to both windings?

Yes. Use each winding’s own current with the same method to size primary and secondary conductors.